When the grid meter misses a phase
In short: leave the “Unmetered grid phase” setting empty, unless your grid meter really doesn’t measure one of the three phases. On a correctly wired installation, setting it makes things worse.
The problem
Section titled “The problem”A three-phase inverter has a grid meter where your house connects to the grid: a smart meter, or current clamps on the cables, measuring what flows in and out on each phase (L1, L2 and L3; SolaX calls them R, S and T).
Gleanvolt works out the surplus from that meter. If the clamp on one phase is missing, loose or on the wrong cable, the meter reads 0 W on that phase, whatever really flows there. Then:
- About a third of the sun you export is invisible. Gleanvolt thinks the house uses it, finds little or no surplus, and the solar modes don’t start the car, even on a sunny afternoon with a full battery.
- About a third of the car’s draw is invisible. Gleanvolt thinks the sun covers the car while it quietly charges from the grid.
Signs to look for
Section titled “Signs to look for”- A sunny afternoon, the home battery full, and yet the Overview shows a large House figure and almost no surplus. Solar + grid or Forecasted doesn’t start.
- The House figure rises and falls with the sun.
- While the car charges, the House figure shows a dash, or the grid import is smaller than what the car alone takes.
- Your electricity bill shows more bought electricity than Gleanvolt or your inverter’s app.
How to check
Section titled “How to check”Look at the grid meter’s readings per phase while the sun shines: on the inverter’s display, in its app, or ask your installer.
- Wired correctly: all three phases show values that change.
- One phase blind: one phase stays at 0 W all the time, while the inverter’s own output on that phase clearly isn’t zero.
If you can’t check it, leave the setting empty and ask your installer.
What to enter
Section titled “What to enter”On Settings, under the inverter, enter the blind phase in Unmetered grid phase: L1, L2 or
L3 (or SolaX’s R, S or T). Press Save, then Restart.
Gleanvolt then estimates that phase from what it does know: the inverter’s own output on it, the car’s share of the charge, and the house’s use on the other two phases. It is an estimate, and a big appliance on that phase puts it off for a while, but it is far better than a third of everything missing.
The real fix
Section titled “The real fix”Have an electrician fit or fix the clamp. When the meter measures all three phases, empty the setting and restart. Left set on a meter that sees every phase, it counts that phase twice.